34
Contact I/O Specifications (All Units)
Section 2-2
Note
Information on input interrupts applies to both Input Interrupt Mode and
Counter Mode. Only single-phase inputs are possible for interrupt inputs.
2-2-2
I/O Connector Pin Arrangement
Contact
outputs
Number of outputs
8 outputs (used as normal outputs only)
Output type
Sinking (NPN)
Switching capacity
4.5 to 30 VDC, 0.3 A per output
Maximum inrush
current
3.0 A per point, 10 ms max.
Leakage current
0.1 mA max.
Residual voltage
0.4 V max.
ON delay time
0.1 ms max.
OFF delay time
1 ms max.
External power
supply
4.5 to 26.4 VDC
Circuit configura-
tion
Pin arrangement
Row B
Pin
Row A
External input 0 (Interrupt input or
normal input; bit 00000)
12
External input 2 (Interrupt input or
normal input; bit 00002)
External input 1 (Interrupt input or
normal input; bit 00001)
11
External input 3 (Interrupt input or
normal input; bit 00003)
Common for external inputs 0 to 3
10
Common for external inputs 4 to 11
External input 4
(Normal input; bit 00004)
9
External input 8
(Normal input; bit 00008)
External input 5
(Normal input; bit 00005)
8
External input 9
(Normal input; bit 00009)
External input 6
(Normal input; bit 00006)
7
External input 10
(Normal input; bit 00010)
External input 7
(Normal input; bit 00007)
6
External input 11
(Normal input; bit 00011)
External output 0
(Normal output; bit 00100)
5
External output 4
(Normal output; bit 00104)
External output 1
(Normal output; bit 00101)
4
External output 5
(Normal output; bit 00105)
External output 2
(Normal output; bit 00102)
3
External output 6
(Normal output; bit 00106)
External output 3
(Normal output; bit 00103)
2
External output 7
(Normal output; bit 00107)
Common for external outputs 0 to 7
1
Power supply for external outputs 0
to 7
Item
Specifications
Customizable Counter Unit
Output
indicator
OUT00
+V
OUT07
COM
Inter
nal circuit
to
Summary of Contents for CS1W-HCA12-V1
Page 2: ......
Page 6: ...vi...
Page 20: ...xx Conformance to EC Directives 7...
Page 38: ...18 Models and System Configurations Section 1 2...
Page 78: ...58 Fail safe Circuits Section 3 5...
Page 138: ...118 AR Area Section 6 4...
Page 204: ...184 Improved Instructions Section 7 14...
Page 222: ...202 Cycle Time Section 8 3...
Page 240: ...220 Troubleshooting Flowcharts Section 9 5...
Page 244: ...224 Precautions when Using the CX Programmer Appendix A...
Page 252: ......
Page 253: ......