68
Words Allocated in DM Area
Section 4-3
4-3-2
DM Area Allocation Details
Initial Setting Area (m to m+9)
Word Bits
Function
Contents
Setting
Condition
m
00 to 07
RUN/STOP
command
enable/disable
and operating
mode at startup
Operating mode at
startup
Operating mode
specification after
startup
Operation for error
at PLC (SR 24915
turns ON)
00 Hex
RUN/STOP
command
enabled
Determined by the status of the RUN/
STOP Command Bit (n, bit 00). The
operating mode can be switched
between RUN mode and MONITOR
mode using the Programming Device
connected to the Customizable
Counter Unit.
The RUN/STOP
Command Bit (n,
bit 00) turns OFF
and Customizable
Counter Unit oper-
ation stops.
Note:
There are
errors for which
the RUN/STOP
Command Bit may
not turn OFF. For
details, refer to
9-3
Troubleshooting
Tables
.
01 Hex
RUN/STOP
command
disabled
Determined by the
operating mode
specification of the
Programming
Console.
Note:
If there is no
Programming
Console con-
nected or if the
Programming
Device connec-
tion switch on the
front of the Unit is
set to OFF, the
mode is automati-
cally set to RUN
mode.
Determined by
commands from
the Programming
Device (CX- Pro-
grammer or the
Programming
Console).
Note:
The RUN/
STOP command
(n, bit 00) is dis-
abled.
Customizable
Counter Unit oper-
ation continues.
02 Hex
PROGRAM mode
03 Hex
MONITOR mode
04 Hex
RUN mode
08 to 15
(Reserved by system.)
---
Summary of Contents for CS1W-HCA12-V1
Page 2: ......
Page 6: ...vi...
Page 20: ...xx Conformance to EC Directives 7...
Page 38: ...18 Models and System Configurations Section 1 2...
Page 78: ...58 Fail safe Circuits Section 3 5...
Page 138: ...118 AR Area Section 6 4...
Page 204: ...184 Improved Instructions Section 7 14...
Page 222: ...202 Cycle Time Section 8 3...
Page 240: ...220 Troubleshooting Flowcharts Section 9 5...
Page 244: ...224 Precautions when Using the CX Programmer Appendix A...
Page 252: ......
Page 253: ......