156
Analog Input Functions
Section 7-9
7-9-4
Related Areas
Unit Setup Area
Auxiliary Memory Area
Address
Bits
Function
Details
DM 6612
00 to 07
Analog input
Analog input range
00 Hex:
-
10 to +10 V
01 Hex: 0 to 10 V
02 Hex: 1 to 5 V (4 to 20 mA)
03 Hex: 0 to 5 V
DM 6630
08 to 15
Analog inputs
Analog input refresh
method
00 Hex: END refresh
01 Hex: Immediate refresh using PRV instruction
DM 6631
00 to 15
For both analog out-
puts 1 and 2
Adjustment mode
password
5A5A Hex: Adjustment mode enabled
Setting other than 5A5A: Adjustment mode disabled
Address
Bits
Function
Details
Controlled
by
Forced
set/reset
AR 02
00 to 15 Analog input value
Analog input At END refresh or immediate refresh
with instructions, the value input to ana-
log input port 1 is stored with the follow-
ing 4-digit hexadecimal:
• With 0 to 10 V: FE70 to 20D0 Hex
• With 0 to 5 V, 1 to 5 V: FF38 to 1068
Hex
• With
-
10 to +10 V: DDA0 to 2260 Hex
Unit
Disabled
AR 03
00
Analog input status User adjust-
ment
0: No adjustment
1: Adjusted by user
08
Default
adjustment
error
0: No error
1: Error (checked at powering ON)
09
User adjust-
ment data
error
0: No error
1: Error (checked at powering ON)
Summary of Contents for CS1W-HCA12-V1
Page 2: ......
Page 6: ...vi...
Page 20: ...xx Conformance to EC Directives 7...
Page 38: ...18 Models and System Configurations Section 1 2...
Page 78: ...58 Fail safe Circuits Section 3 5...
Page 138: ...118 AR Area Section 6 4...
Page 204: ...184 Improved Instructions Section 7 14...
Page 222: ...202 Cycle Time Section 8 3...
Page 240: ...220 Troubleshooting Flowcharts Section 9 5...
Page 244: ...224 Precautions when Using the CX Programmer Appendix A...
Page 252: ......
Page 253: ......