213
Troubleshooting Flowcharts
Section 9-5
9-5
Troubleshooting Flowcharts
Use the following flowcharts to troubleshoot errors that occur during opera-
tion.
Main Check
Note
Always turn OFF the power to the PLC before replacing Units, wiring, or
cables.
Check for non-fatal errors.
Error
Replace the Cus-
tomizable Count-
er Unit.
Power indicator lit?
RUN indicator lit?
ERC indicator lit
or flashing?
Is I/O sequence
normal?
Operating
environment
normal?
Check for fatal errors.
Check I/O.
Check operating environment.
Lit
Check power supply.
Not lit
Not normal
Not lit
Not normal
Flashing
or lit
Normal
Normal
Not lit
Lit