292
E5ZE Temperature Controller Write Protocol
Appendix F
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Output Value Change Rate Limit (Sequence No. 167 (Hex
00A7))
Writes the output value change rate limits that restrict the rates of change in the control value output.
Send Data Word Allocation (3rd Operand of PMCR(260))
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
0022 (0034 decimal) (fixed)
+1
Unit No. (2 digits Hex)
00 to 0F
+2
Channel 0
Output value lower limit
(4 digits BCD)
0000 to 1000
+3 Channel
0
Output value upper limit
(4 digits BCD)
0000 to 1000
+4
Channel 0
Cooling output value lower limit
(4 digits BCD)
0000 to 1000
+5
Channel 0
Cooling output value upper limit
(4 digits BCD)
0000 to 1000
•
•
•
+32
Channel 7
Cooling output value lower limit
(4 digits BCD)
0000 to 1000
+33
Channel 7
Cooling output value upper limit
(4 digits BCD)
0000 to 1000
First word of
send data
Number of send data words
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
(Undefined)
Unit No.
Output change rate limit
Output change rate limit
Channel 0
Channel 1
Output change rate limit
Channel 2
Output change rate limit
Channel 3
Output change rate limit
Channel 4
Output change rate limit
Channel 5
Output change rate limit
Channel 6
Output change rate limit
Channel 7
Summary of Contents for CJ1W-SCU41
Page 3: ...KX ...
Page 5: ...XK ...
Page 9: ......
Page 19: ......
Page 119: ......
Page 177: ......
Page 187: ......
Page 221: ......
Page 259: ......
Page 317: ......
Page 333: ......
Page 373: ......
Page 395: ......
Page 407: ......
Page 443: ......
Page 463: ......
Page 501: ......
Page 509: ......
Page 513: ......
Page 525: ......