210
CompoWay/F Master Protocol
Appendix B
CompoWay/F Master Protocol Sequences
The CompoWay/F Master Protocol provides six communications sequences that can be used for the following:
• Converting to ASCII data or not converting to ASCII data
• Sending to a specified Unit or broadcasting
• Specifying from the command code or specifying from the subaddress and SID.
Structure of the Protocol
The following table shows the structure of the CompoWay/F Master Protocol.
Note The hexadecimal equivalents of sequences numbers are given in parentheses.
Sequence No. 600 can be used for the normal CompoWay/F Master function (ASCII conversion, specification
from command code).
Refer to the communications specifications for the OMRON CompoWay/F component to which the command is
being sent and set the command code and required data starting at the words specified for the 3rd operand of
PMCR(260).
The relationship between the CompoWay/F command and response frames and the operands of PMCR(260)
is described next.
Sequence
No.
Communications
sequence name
Function
Ladder interface
Send word
allocation
Receive word
allocation
600 (0258)
Send with ASCII conver-
sion, with response
Converts the specified data beginning with
the command code to ASCII and sends it to
the specified Unit. The response is con-
verted to hexadecimal and stored starting at
the specified word.
Yes
Yes
601 (0259)
Broadcast with ASCII
conversion, no response
A broadcast version of sequence No. 600.
No responses are received.
Yes
No
602 (025A)
Send with no conversion
and with response
Sends specified data beginning with the
command code to the specified Unit. The
response is stored starting at the specified
word. This is the same as sequence No.
600 without data conversion and can be
used when conversion is not required.
Yes
Yes
603 (025B)
Broadcast with no con-
version and no response
A broadcast version of sequence No. 602.
No responses are received.
Yes
No
604 (025C)
General-purpose send
with no conversion and
with response
Sends specified data beginning with the
subaddress and SID to the specified Unit.
The response is stored starting at the spec-
ified word. This sequence can be used
whenever it is necessary to specify the sub-
address or SID.
Yes
Yes
605 (025D)
General-purpose broad-
cast with no conversion
and no response
A broadcast version of sequence No. 604.
No responses are received.
Yes
No
Summary of Contents for CJ1W-SCU41
Page 3: ...KX ...
Page 5: ...XK ...
Page 9: ......
Page 19: ......
Page 119: ......
Page 177: ......
Page 187: ......
Page 221: ......
Page 259: ......
Page 317: ......
Page 333: ......
Page 373: ......
Page 395: ......
Page 407: ......
Page 443: ......
Page 463: ......
Page 501: ......
Page 509: ......
Page 513: ......
Page 525: ......