305
E5
#
J Temperature Controller Protocol
Appendix G
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Parameters 2 (Sequence No. 206 (Hex 00CE))
Writes the proportional bands, integral times, and derivative times to multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
Number of units
×
5 + 2
+1
Number of units (4 digits Hex)
0001 to 0019 (1 to 25 decimal)
+2 1st
unit
Unit No. (2 digits BCD)
00 to 31
+3
1st unit
Set point (4 digits BCD)
0000 to 9999
+4
1st unit
Alarm value 1 (4 digits BCD)
0000 to 9999
+5
1st unit
Alarm value 2 (4 digits BCD)
0000 to 9999
+6
1st unit
Heater burnout alarm value 2
(4 digits BCD)
0000 to 9999
+7
2nd unit
Unit No. (2 digits BCD)
00 to 31
•
•
•
+126
(max.)
25th unit
Heater burnout alarm value 2
(4 digits BCD)
0000 to 9999
First word of
send data
Number of send data words
+0
+1
+2
+3
+4
+5
+122
+123
+124
+125
(Undefined)
Unit No.
Proportional band
~
~
Integral time
Proportional band
Integral time
1st unit
31th unit (max.)
Derivative time
Derivative time
Number of units
(Undefined)
Unit No.
Summary of Contents for CJ1W-SCU41
Page 3: ...KX ...
Page 5: ...XK ...
Page 9: ......
Page 19: ......
Page 119: ......
Page 177: ......
Page 187: ......
Page 221: ......
Page 259: ......
Page 317: ......
Page 333: ......
Page 373: ......
Page 395: ......
Page 407: ......
Page 443: ......
Page 463: ......
Page 501: ......
Page 509: ......
Page 513: ......
Page 525: ......