276
E5ZE Temperature Controller Read Protocol
Appendix E
Receive Data Word Allocation (4th Operand of PMCR(260))
Read Heater Current and SSR Leakage Current
(Sequence No.121 (Hex 0079))
Reads the heater currents and SSR leakage currents and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
Offset
Contents (data format)
Data
+0
Number of receive data words
(4 digits Hex)
0011 (0017 decimal)
+1
Channel 0
Heater burnout detection current
(4 digits BCD)
0000 to 0500
+2 Channel
0
SSR failure detection current
(4 digits BCD)
0000 to 0500
•
•
•
+15
Channel 7
Heater burnout detection current
(4 digits BCD)
0000 to 0500
+16
Channel 7
SSR failure detection current
(4 digits BCD)
0000 to 0500
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
0002 (fixed)
+1
Unit No. (2 digits Hex)
00 to 0F
Receive data
storage words
Number of receive data words
+0
+1
+2
+3
+4
+15
+16
Heater burnout detection current
~
~
SSR failure detection current
Heater burnout detection current
SSR failure detection current
Channel 0
Channel 7
Heater burnout detection current
SSR failure detection current
Channel 1
First word of
send data
Number of send data words
+0
+1
(Undefined)
Unit No.
Receive data
storage words
Number of receive data words
+0
+1
+2
+3
+4
+15
+16
Heater current
~
~
SSR leakage current
Heater current
SSR leakage current
Channel 0
Channel 7
Heater current
SSR leakage current
Channel 1
Summary of Contents for CJ1W-SCU41
Page 3: ...KX ...
Page 5: ...XK ...
Page 9: ......
Page 19: ......
Page 119: ......
Page 177: ......
Page 187: ......
Page 221: ......
Page 259: ......
Page 317: ......
Page 333: ......
Page 373: ......
Page 395: ......
Page 407: ......
Page 443: ......
Page 463: ......
Page 501: ......
Page 509: ......
Page 513: ......
Page 525: ......