216
CompoWay/F Master Protocol
Appendix B
Broadcast with No Conversion and No Response
(Sequence No. 603 (Hex 025B))
This sequence broadcasts the specified data beginning with the command code No responses are received
and no conversions are performed on the send data.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
None. (Specify a dummy value for the operand, such as #0000.)
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
0005 to 00FA Hex (5 to 250 decimal)
+1
(Undefined)
---
+2 MRC
(2 digits Hex)
SRC
(2 digits Hex)
Set the command code for the required ser-
vice
+3
Number of send bytes (4 digits Hex)
Number of data bytes from the next byte
after the command code until the byte just
before the ETX.
0000 to 01EC Hex (0 to 492 decimal)
+4
on
Send data
The data specified in hexadecimal here is
not converted and the number of bytes
specified in S+3 is sent.
+0
+1
+2
+3
+4
+5
+6 etc.
Send data
First word of
send data
Number of send data words
+0
+1
+2
+3
+4
(Undefined)
MRC
SRC
Number of send bytes
Summary of Contents for CJ1W-SCU41