E5ZE Temperature Controller Write Protocol
Appendix F
Write Alarm Temperature (Setting Unit 0.1) (Sequence No. 157
(Hex 009D))
Writes the alarm temperatures using a setting unit of 0.1 (5 digits)
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
0022 (0034 decimal) (fixed)
+1
Unit No. (2 digits Hex)
00 to 0F
+2
Channel 0
Alarm 1 set value (rightmost 4 digits)
(4 digits BCD)
0000 to 9999
+3 Channel
0
Alarm 1 set value (leftmost 1 digits)
(4 digits BCD)
0000 to 0009
+4
Channel 0
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
0000 to 9999
+5
Channel 0
Alarm 2 set value (leftmost 1 digits)
(4 digits BCD)
0000 to 0009
•
•
•
+32
Channel 7
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
0000 to 9999
+33
Channel 7
Alarm 2 set value (leftmost 1 digits)
(4 digits BCD)
0000 to 0009
First word of
send data
Number of send data words
+0
+1
+2
+3
+4
+5
+30
+31
+32
+33
(Undefined)
Unit No.
Alarm 1 set value (rightmost 4 digits)
~
~
Alarm 1 set value (leftmost 1 digit)
Alarm 1 set value (rightmost 4 digits)
Alarm 1 set value (leftmost 1 digit)
Channel 0
Channel 7
Alarm 2 set value (rightmost 4 digits)
Alarm 2 set value (leftmost 1 digit)
Alarm 2 set value (rightmost 4 digits)
Alarm 2 set value (leftmost 1 digit)
Summary of Contents for CJ1W-SCU41
Page 3: ...KX ...
Page 5: ...XK ...
Page 9: ......
Page 19: ......
Page 119: ......
Page 177: ......
Page 187: ......
Page 221: ......
Page 259: ......
Page 317: ......
Page 333: ......
Page 373: ......
Page 395: ......
Page 407: ......
Page 443: ......
Page 463: ......
Page 501: ......
Page 509: ......
Page 513: ......
Page 525: ......