K Digital Controller Read Protocol
Appendix C
RS-485 Connection
Note 1.
The communications configuration is a one-to-one configuration or a one-to-N configuration. In the
one-to-N configuration, up to 32 units including the Serial Communications Unit/Board can be con-
nected.
2.
The maximum cable length is 500 m. Use a shielded twisted-pair cable for the cable (AWG28i or
greater).
3.
Connect a terminator only at both ends of the transmission path. For instance, in the example shown
below, connect a terminator to the Serial Communications Unit/Board and unit No.30 and do not con-
nect any terminator to units No.0 to No.29. Use a resistance of 120
Ω
(1/2W) for the terminators (the
total resistance of both ends must be 54
Ω
or more).
RS-485 port
E5
#
K
E5
#
K
E5
#
K
Up to 31 units can be connected.
→
→
→
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
RS-485
RS-485
RS-485
Terminator (120
Ω
, 1/2 W)
A<B: [1] Mark
A>B: [0] Space
Serial Communications Board/Unit
Pin No.
Shielded cable
E5CK (No. 30)
Terminal No.
Terminal No.
E5CK (No. 0)
RS-485: D-sub
9 pin female
RS-485: Terminal block
RS-485: Terminal block
1
2
FG
13
14
A
B
13
14
A
B
Summary of Contents for CJ1W-SCU41
Page 3: ...KX ...
Page 5: ...XK ...
Page 9: ......
Page 19: ......
Page 119: ......
Page 177: ......
Page 187: ......
Page 221: ......
Page 259: ......
Page 317: ......
Page 333: ......
Page 373: ......
Page 395: ......
Page 407: ......
Page 443: ......
Page 463: ......
Page 501: ......
Page 509: ......
Page 513: ......
Page 525: ......