229
E5
#
K Digital Controller Read Protocol
Appendix C
Read SP Ramp Time Unit and Set Value (Sequence No. 011 (Hex
000B))
Reads the SP ramp time unit and SP ramp set value and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
Read LBA Detection Time (Sequence No. 012 (Hex 000C))
Reads the LBA (loop break alarm) detection time and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
0002 (fixed)
+1
Unit No. (2 digits BCD)
00 to 31
Offset
Contents (data format)
Data
+0
Number of receive data words
(4 digits Hex)
0003
+1
SP ramp time unit (4 digits BCD)
0000: s, 0001: hr
+2
SP ramp set value (4 digits BCD)
0000 to 9999
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
0002 (fixed)
+1
Unit No. (2 digits BCD)
00 to 31
Offset
Contents (data format)
Data
+0
Number of receive data words
(4 digits Hex)
0002
+1
LBA detection time (4 digits BCD)
0000 to 9999
First word of
send data
Number of send data words
+0
+1
(Undefined)
Unit No.
Receive data
storage words
Number of receive data words
+0
+1
+2
SP ramp time unit
SP ramp set value
First word of
send data
Number of send data words
+0
+1
(Undefined)
Unit No.
Receive data
storage words
Number of receive data words
+0
+1
LBA detection time
Summary of Contents for CJ1W-SCU41
Page 3: ...KX ...
Page 5: ...XK ...
Page 9: ......
Page 19: ......
Page 119: ......
Page 177: ......
Page 187: ......
Page 221: ......
Page 259: ......
Page 317: ......
Page 333: ......
Page 373: ......
Page 395: ......
Page 407: ......
Page 443: ......
Page 463: ......
Page 501: ......
Page 509: ......
Page 513: ......
Page 525: ......