K Digital Controller Read Protocol
Appendix C
Receive Data Word Allocation (4th Operand of PMCR(260))
Read Level 1 Parameters 1 (Sequence No. 019 (Hex 0013))
Reads parameters in level 1 (alarm value 1, alarm value 2, alarm value 3, proportional band, integral time, and
derivative time) from multiple units and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
Offset
Contents (data format)
Data
+0
Number of receive data words
(4 digits Hex)
Number of units
×
5 + 1
+1
1st unit
Process value (4 digits BCD)
Scaling lower limit to upper limit
+2
1st unit
Set point during SP ramp
(4 digits BCD)
Set point lower limit to upper limit
+3
1st unit
MV (heating) (4 digits BCD)
F050 to 1050
F indicates a negative value.
0000 to 1050 for heating/cooling con-
trol
+4
1st unit
MV (cooling) (4 digits BCD)
0000 to 1050
+5
1st unit
Set point (4 digits BCD)
Set point lower limit to upper limit
•
•
•
+40
(max.)
8th unit
Set point (4 digits BCD)
Set point lower limit to upper limit
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
Number of units + 2
+1
Number of units (4 digits Hex)
0001 to 0008
+2 to 9
Unit No. (2 digits BCD)
00 to 31
Process value
Receive
data storage
words
Number of receive data words
+0
+1
+2
+3
+4
+5
+36
+37
+38
+39
+40
Process value
Set point during SP ramp
MV (heating)
MV (cooling)
~
~
Set point during SP ramp
MV (heating)
MV (cooling)
Set point
1st unit
8th unit (max.)
Set point
(Undefined)
Unit No.
First word of
send data
Number of send data words
+0
+1
+2
+3
+9
(Undefined)
Unit No.
Number of units
(Undefined)
Unit No.
~
~
(max.)
Summary of Contents for CJ1W-SCU41
Page 3: ...KX ...
Page 5: ...XK ...
Page 9: ......
Page 19: ......
Page 119: ......
Page 177: ......
Page 187: ......
Page 221: ......
Page 259: ......
Page 317: ......
Page 333: ......
Page 373: ......
Page 395: ......
Page 407: ......
Page 443: ......
Page 463: ......
Page 501: ......
Page 509: ......
Page 513: ......
Page 525: ......