248
E5
#
K Digital Controller Write Protocol
Appendix D
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Level 0 Parameters (Sequence No. 065 (Hex 0041))
Writes parameters (set points) in level 0 to multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
Number of units
×
2 + 2
+1
Number of units (4 digits Hex)
0001 to 0008
+2 1st
unit
Unit No. (2 digits BCD)
00 to 31
+3
1st unit
Set point (4 digits BCD)
Set point lower limit to upper limit
•
•
•
+17
(max.)
8th unit
Set point (4 digits BCD)
Set point lower limit to upper limit
(Undefined)
Unit No.
First word of
send data
Number of send data words
+0
+1
+2
+3
+4
+5
+16
+17
(Undefined)
Unit No.
Number of units
(Undefined)
Unit No.
~
~
Set point
Set point
Set point
1st unit
2nd unit
8th unit (max.)