K Digital Controller Read Protocol
Appendix C
Receive Data Word Allocation (4th Operand of PMCR(260))
Read Level 1 Parameters 2 (Sequence No. 020 (Hex 0014))
Reads parameters in level 1 (cooling coefficient, dead band, manual reset value, hysteresis (heating), hystere-
sis (cooling), control period (heating), and control period (cooling)) from multiple units and stores the results in
the specified words.
Offset
Contents (data format)
Data
+0
Number of receive data words
(4 digits Hex)
Number of units
×
6 + 1
+1
1st unit
Alarm value 1 (4 digits BCD)
A999 to 9999
F indicates a negative value and A indi-
cates –1.
+2
1st unit
Alarm value 2 (4 digits BCD)
A999 to 9999
F indicates a negative value and A indi-
cates –1.
+3
1st unit
Alarm value 3 (4 digits BCD)
A999 to 9999
F indicates a negative value and A indi-
cates –1.
+4
1st unit
Proportional band
(4 digits BCD)
0001 to 9999
+5
1st unit
Integral time (4 digits BCD)
0000 to 3999
+6
1st unit
Derivative time (4 digits BCD)
0000 to 3999
•
•
•
+48
(max.)
8th unit
Derivative time (4 digits BCD)
0000 to 3999
Alarm value 1
Receive
data storage
words
Number of receive data words
+0
+1
+2
+3
+4
+5
+6
+43
+44
+45
+46
+47
+48
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
~
~
Alarm value 2
Alarm value 3
Proportional band
Integral time
1st unit
8th unit (max.)
Derivative time
Derivative time
Summary of Contents for CJ1W-SCU41
Page 3: ...KX ...
Page 5: ...XK ...
Page 9: ......
Page 19: ......
Page 119: ......
Page 177: ......
Page 187: ......
Page 221: ......
Page 259: ......
Page 317: ......
Page 333: ......
Page 373: ......
Page 395: ......
Page 407: ......
Page 443: ......
Page 463: ......
Page 501: ......
Page 509: ......
Page 513: ......
Page 525: ......