290
E5ZE Temperature Controller Write Protocol
Appendix F
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Ramp Value (Sequence No. 164 (Hex 00A4))
Writes the ramp values.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Manual Output Value (Sequence No. 165 (Hex 00A5))
Writes the manual output values for control output in manual operation.
Send Data Word Allocation (3rd Operand of PMCR(260))
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
0012 (0018 decimal) (fixed)
+1
Unit No. (2 digits Hex)
00 to 0F
+2
Channel 0
Ramp value (3 digits BCD)
000 to 999
+3 Channel
0
Time unit (one ASCII character)
S: Seconds; M: Minutes; H: Hours
+4
Channel 1
Ramp value (3 digits BCD)
000 to 999
+5 Channel
1
Time unit (one ASCII character)
S: Second M: Minute H: Hour
•
•
•
+16
Channel 7
Ramp value (3 digits BCD)
000 to 999
+17
Channel 7
Time unit (one ASCII character)
S: Seconds; M: Minutes; H: Hours
First word of
send data
Number of send data words
+0
+1
+2
+3
+4
+5
+16
+17
(Undefined)
Unit No.
Ramp value
(Undefined)
~
~
Channel 0
Channel 7
Channel 1
Ramp value
Time unit
(Undefined)
(Undefined)
Ramp value
Time unit
(Undefined)
(Undefined)
Time unit
(Undefined)
First word of
send data
Number of send data words
+0
+1
+2
+3
+4
+5
+16
+17
(Undefined)
Unit No.
Output value
~
~
Cooling output value
Output value
Cooling output value
Channel 0
Channel 7
Output value
Cooling output value
Channel 1
Summary of Contents for CJ1W-SCU41
Page 3: ...KX ...
Page 5: ...XK ...
Page 9: ......
Page 19: ......
Page 119: ......
Page 177: ......
Page 187: ......
Page 221: ......
Page 259: ......
Page 317: ......
Page 333: ......
Page 373: ......
Page 395: ......
Page 407: ......
Page 443: ......
Page 463: ......
Page 501: ......
Page 509: ......
Page 513: ......
Page 525: ......