315
Appendix H
ES100
#
Digital Controller Protocol
The ES100
#
Digital Controller Protocol controls in remote mode and reads various settings from the Controller
connected to the Serial Communications Unit/Board via RS-232C or RS-422A/485 cable.
Note Negative values cannot be written. All values must be set as unsigned BCD.
Structure of the Protocol
The structure of the ES100
#
Digital Controller Protocol is shown below.
Sequence
No.
Transmission
sequence name
Function
Ladder interface
Send word
allocation
Receive word
allocation
250 (00FA)
Read event data
Reads events 1 to 10 in the variable area.
Yes
Yes
251 (00FB)
Read time signals
Reads time signals 1 to 10 in the variable
area.
Yes
Yes
252 (00FC)
Read error detection
data
Reads error groups 1 to 15 in the variable
area.
Yes
Yes
253 (00FD)
Read heater burnout
data
Reads the heater burnout alarm.
Yes
Yes
254 (00FE)
Read PV data
Reads PV data in the variable area.
Yes
Yes
255 (00FF)
Read SP data
Reads SP data in the variable area.
Yes
Yes
256 (0100)
Read MV
Reads the MV in the variable area.
Yes
Yes
257 (0101)
Read control monitor
data
Reads control monitor data (SP, PV, and MV)
in the variable area.
Yes
Yes
258 (0102)
Read adjustment
parameters
Reads adjustment parameters in the parame-
ter area.
Yes
Yes
259 (0103)
Write adjustment
parameters
Writes adjustment parameters in the parame-
ter area.
Yes
No
260 (0104)
Read PID control
parameters 1
Reads PID parameters No. 1 to 4 from the
PID control parameters in the parameter
area.
Yes
Yes
261 (0105)
Read PID control
parameters 2
Reads PID parameters No. 5 to 8 from the
PID control parameters in the parameter
area.
Yes
Yes
262 (0106)
Write PID control
parameters 1
Writes PID parameters No. 1 to 4 from PID
control parameters in the parameter area.
Yes
No
263 (0107)
Write PID control
parameters 2
Writes PID parameters No. 5 to 8 from PID
control parameters in the parameter area.
Yes
No
264 (0108)
Read local SP
Reads the local SP in the program parameter
area.
Yes
Yes
265 (0109)
Write local SP
Writes local SP in the program parameter
area.
Yes
No
266 (010A)
Read program parame-
ters
Reads local SP, step time, PID No. wait code,
and events 1 to 10 set values in the program
parameter area.
Yes
Yes
267 (010B)
Write program parame-
ters
Writes the local SP, step time, PID No., wait
code, and event 1 to 10 set values in the pro-
gram parameter area.
Yes
No
268 (010C)
Remote setting mode
Switches the setting mode to remote setting.
Yes
No
269 (010D)
Local setting mode
Switches the setting mode to local setting.
Yes
No
270 (010E)
External setting mode
Switches the setting mode to external setting.
Yes
No
Summary of Contents for CJ1W-SCU41
Page 3: ...KX ...
Page 5: ...XK ...
Page 9: ......
Page 19: ......
Page 119: ......
Page 177: ......
Page 187: ......
Page 221: ......
Page 259: ......
Page 317: ......
Page 333: ......
Page 373: ......
Page 395: ......
Page 407: ......
Page 443: ......
Page 463: ......
Page 501: ......
Page 509: ......
Page 513: ......
Page 525: ......