266
E5ZE Temperature Controller Read Protocol
Appendix E
Read Control Period (Sequence No. 105 (Hex 0069))
Reads the control periods and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
Offset
Contents (data format)
Data
+0
Number of receive data words
(4 digits Hex)
0019 (0025 decimal)
+1
Channel 0
Constant P (4 digits BCD)
0000 to 9999
+2 Channel
0
Constant I (4 digits BCD)
0000 to 3999
+3
Channel 0
Constant D (4 digits BCD)
0000 to 3999
•
•
•
+22
Channel 7
Constant P (4 digits BCD)
0000 to 9999
+23
Channel 7
Constant I (4 digits BCD)
0000 to 3999
+24
Channel 7
Constant D (4 digits BCD)
0000 to 3999
Offset
Contents (data format)
Data
+0
Number of send data words
(4 digits Hex)
0002 (fixed)
+1
Unit No. (2 digits Hex)
00 to 0F
Offset
Contents (data format)
Data
+0
Number of receive data words
(4 digits Hex)
0011 (0017 decimal)
+1
Channel 0
Control period (4 digits BCD)
0001 to 0099
+2 Channel
0
Cooling control period
(4 digits BCD)
0001 to 0099
•
•
•
+15
Channel 7
Control period (4 digits BCD)
0001 to 0099
+16
Channel 7
Cooling control period
(4 digits BCD)
0001 to 0099
First word of
send data
Number of send data words
+0
+1
(Undefined)
Unit No.
Receive data
storage words
Number of receive data words
+0
+1
+2
+3
+4
+15
+16
Control period
~
~
Cooling control period
Control period
Cooling control period
Channel 0
Channel 7
Control period
Cooling control period
Channel 1
Summary of Contents for CJ1W-SCU41
Page 3: ...KX ...
Page 5: ...XK ...
Page 9: ......
Page 19: ......
Page 119: ......
Page 177: ......
Page 187: ......
Page 221: ......
Page 259: ......
Page 317: ......
Page 333: ......
Page 373: ......
Page 395: ......
Page 407: ......
Page 443: ......
Page 463: ......
Page 501: ......
Page 509: ......
Page 513: ......
Page 525: ......