![background image](http://html1.mh-extra.com/html/omron/c200hw-srm21-v1-cs1w-srm21/c200hw-srm21-v1-cs1w-srm21_operation-manual_742333309.webp)
288
Sensor Terminals
Section 5-5
The total current consumption of the sensors must be less than 500 mA.
Input Specifications
Output Specifications
Item
Specification
ON voltage
12 V DC min. (between each input terminal and V
CC
, the
external sensor power supply)
OFF voltage
4 V DC max. (between each input terminal and V
CC
, the
external sensor power supply)
OFF current
1 V max.
Input current
10 mA max./point
ON delay time
1 ms max.
OFF delay time
1.5 ms max.
Insulation resistance
20 M
Ω
min. at 250 V DC (between insulated circuits)
Insulation method
Photocoupler
Item
Specification
Rated output current
20 mA max.
Residual voltage
1 V max. (between each output terminal and VCC, the
external sensor power supply)
Leakage current
0.1 mA max. (between each output terminal and VCC,
the external sensor power supply)
ON delay time
1.0 ms max.
OFF delay time
1.5 ms max.
Insulation resistance
20 M
Ω
min. at 250 V DC
Insulation method
Photocoupler