324
Analog Output Terminals
Section 5-8
0 to 5 V
Values 0000 to 1770 Hex (0 to 6000) correspond to voltages between 0 and
5 V. The output range is –0.25 to 5.25 V.
0 to 10 V
Values 0000 to 1770 Hex (0 to 6000) correspond to voltages between 0 and
10 V. The output range is –0.5 to 10.5 V.
–10 to 10 V
Values F448 to 0BB8 Hex (–3000 to 3000) correspond to voltages between –
10 and 10 V. The output range is –11 to 11 V.
Negative voltages are specified as 2
’
s complement (16 bits).
Voltage
Hexadecimal
(decimal)
conversion data
FED4
(–300)
189C
(6300)
1770
(6000)
0000 (0)
0 V
–0.25 V
5.25 V
5 V
8000
7FFF
Voltage
Hexadecimal
(decimal)
conversion data
FED4
(–300)
189C
(6300)
1770
(6000)
0000 (0)
0 V
–0.5 V
10.5 V
10 V
8000
7FFF
Voltage
Hexadecimal
(decimal)
conversion data
F31C
(–3300)
F448
(–3000)
0CE4
(3300)
0BB8
(3000)
0000 (0)
0 V
11 V
10 V
–10 V
–11 V
8000
7FFF