169
Remote Terminals
Section 5-1
Terminal Arrangement
and Wiring
Install the following M3 crimp terminals on the signal wires and connect to the
terminal block.
Note
Tighten the terminal block screws to the specified tightening torque of
0.5 N
⋅
m
.
The following diagram shows the terminal arrangement and wiring for the
SRT
@
-OD04.
Note
1.
The V terminals (terminal numbers 4, 5, 6, 7, and 11) are all connected in-
ternally. When I/O power is supplied to terminals 11 and 3, power can be
supplied to output devices from terminals 4, 5, 6, and 7.
When the power supply exceeds 1.0 A, provide an external power supply
to the I/O power supply instead of providing the supply from the terminals.
2.
When inductive loads such as solenoids and valves are used, either use
ones with built-in diodes that absorb the back-electromotive force or con-
nect a diode externally.
The following diagram shows the terminal arrangement and wiring for the
SRT
@
-OD04-1.
Note
1.
G terminals (terminal numbers 3 and 4, 5, 6, 7) are all connected internally.
When I/O power is supplied to terminals 11 and 3, power can be provided
to output devices from terminals 4, 5, 6, and 7.
6.0mm max.
6.0mm max.
CompoBus/S
24 V DC
CompoBus/S
communications
CompoBus/S
communications
power supply
I/O power supply
Solenoid
Valve
Solenoid
CompoBus/S
communications
CompoBus/S
communications
power supply
I/O power supply
Solenoid
Valve
CompoBus/S
24 V DC