177
Remote Terminals
Section 5-1
Terminal Arrangement
and Wiring
Install the following M3 crimp terminals on the signal wires and connect to the
terminal block.
Note
Tighten the terminal block screws to the specified tightening torque of
0.5 N
⋅
m
.
The following diagram shows the terminal arrangement and wiring for the
SRT
@
-OD16T.
The following diagram shows the terminal arrangement and wiring for the
SRT
@
-OD16T-1.
Note
1.
The V terminals V1 and V2 are not connected internally, and neither are
the G terminals G1 and G2 (I/O power supply). Care must be taken when
connecting them.
2.
Do not allow the current between V1 and G1 or between V2 and G2 to ex-
ceed 4 A.
3.
When using inductive loads such as solenoids and valves, either use loads
with built-in diodes that absorb the back-electromotive force or connect a
diode externally.
6.0mm max.
6.0mm max.
Solenoid,
valve
CompoBus/S
communications
power supply
CompoBus/S
communications
Solenoid,
valve
Solenoid,
valve
Solenoid,
valve
Solenoid,
valve
CompoBus/S
communications
power supply
CompoBus/S
communications
Solenoid,
valve
Solenoid,
valve
Solenoid,
valve