278
Water-resistant Terminals
Section 5-4
Note
This is the current consumption when all the maximum simultaneous output
points are ON, excluding the current consumption of external loads.
Output Specifications
Slave Components
The following diagram shows the main components of the SRT2-OD
@@
CL
(-
@
) Water-resistant Terminals with Transistor Outputs. The functions of these
components are described below.
Vibration resistance
10 to 150 Hz, 0.7-mm double amplitude or 50 m/s
2
Shock resistance
150 m/s
2
Dielectric strength
500 V AC (between insulated circuits)
Insulation resistance
20 M
Ω
min. (between insulated circuits)
Ambient temperature
Operating: –10 to 55
°
C (with no icing or condensation)
Storage: –25 to 65
°
C (with no icing or condensation)
Ambient humidity
Operating: 25% to 85% (with no condensation)
Storage: 25% to 85% (with no condensation)
Operating environment
No corrosive gases
Enclosure rating
IP67
Mounting method
M5 screws
Terminal strength
100N
Node number settings
The node number is set on a rotary switch. (Set the node
number before turning ON the Slave.)
Weight
SRT2-OD04CL (-1): 180 g max.
SRT2-OD08CL (-1): 240 g max.
Item
Specification
Item
Specifications
Output current
OD04CL (-1): 0.3 A/point 1.2 A/common
OD08CL (-1): 0.3 A/point 2.4 A/common
Residual voltage
1.2 V max.
Leakage current
0.1 mA max.
ON delay time
0.5 ms max.
OFF delay time
1.5 ms max.
Insulation method
Photocoupler
Output indicator
LED (yellow)
Number of circuits
OD04CL (-1): 4 points/single common circuit
OD08CL (-1): 8 points/single common circuit
CompoBus/S Indicators
Indicate the status of the Slave and communications.
Rotary Switch
Used to set the
node number
DIP switch
The DIP switch's pins have the follow-
ing functions:
Pins 1 to 2: Reserved (Always OFF.)
Pin 3: Communications mode setting
Pin 4: Reserved (Always OFF.)
External Power Supply Connector
Connect I/O power supply for output.
Output Connectors
Connect the cables from relays and display terminals
here. The SRT2-OD04CL has 4 connectors and
SRT2-OD08CL has 8 connectors.
Output Indicators
Indicate the status of
each output.
(Lit when the output
is ON.)
Communications Connector
Used to connect CompoBus/S communica-
tions data (BD H, BD L) and communica-
tions power supply
(see page 284).