![background image](http://html1.mh-extra.com/html/omron/c200hw-srm21-v1-cs1w-srm21/c200hw-srm21-v1-cs1w-srm21_operation-manual_742333391.webp)
370
Checking Operations of CS-series and CJ-series Master Units
Section 6-3
+6
00
Output Slave Verification
Error: Slave Missing
OUT0
When the Slave registration
function is enabled, the bit
corresponding to the node
number of the Output Slave
that caused the verification
error (Slave missing) will be
turned ON.
Bits 00 to 15 correspond to
Output Slave node numbers 1
to 15. When the Slave that
caused the verification error
joins the network, the bit will
automatically turned OFF.
The bits in the Special I/O
Unit Area correspond to the
node numbers actually used
by the Slaves. Therefore, for
Slaves with 16 points or
higher, the bits other than
those set for the node number
may also be turned ON. For
example, the two consecutive
bits used by a 16-point Slave
or the four consecutive bits
used by a 32-point Slave may
be turned ON at the same
time.
01
OUT1
02
OUT2
to
to
13
OUT13
14
OUT14
15
OUT15
+7
00
Input Slave Verification
Error: Slave Missing
IN0
When the Slave registration
function is enabled, the bit
corresponding to the node
number of the Input Slave that
caused the verification error
(Slave missing) will be turned
ON.
Bits 00 to 15 correspond to
Input Slave node numbers 1
to 15. When the Slave that
caused the verification error
joins the network, the bit will
automatically turned OFF.
01
IN1
02
IN2
to
to
13
IN13
14
IN14
15
IN15
+8
00
Output Slave Verification
Error: Unregistered Slave
in Network
OUT0
When the Slave registration
function is enabled, the bit
corresponding to the node
number of the Output Slave
where a verification error
(unregistered Slave in net-
work) will be turned ON.
Bits 00 to 15 correspond to
Output Slave node numbers 1
to 15.
Once a bit has been turned
ON the status will be held until
the power is turned OFF and
ON again or the Unit is
restarted.
01
OUT1
02
OUT2
to
to
13
OUT13
14
OUT14
15
OUT15
+9
00
Input Slave Verification
Error: Unregistered Slave
in Network
IN0
When the Slave registration
function is enabled, the bit
corresponding to the node
number of the Input Slave
where a verification error
(unregistered Slave in net-
work) will be turned ON.
Bits 00 to 15 correspond to
Input Slave node numbers 1
to 15.
Once a bit has been turned
ON the status will be held until
the power is turned OFF and
ON again or the Unit is
restarted.
01
IN1
02
IN2
to
to
13
IN13
14
IN14
15
IN15
Word
Bit
Name
Function