49
I/O Response Time Characteristics
Section 2-5
Ts
(IN-max)
:
Communications cycle input time
Ts
(OUT-max)
: Communications cycle output time
T
M-IN
:
Input processing time in the Master
CS-series Master Units
Note
Add another 15
µ
s
to the values shown in the table when using the
Slave registration function or communications stop mode.
CJ-series Master Units
Note
Add another 15
µ
s
to the values shown in the table when using the
Slave registration function or communications stop mode.
T
M-out-max
: Maximum output processing time in the Master
CS-series Master Units
Master
Usable node
number setting
Communications cycle time
High-speed
Communica-
tions Mode
Long-dis-
tance Commu-
nications
Mode
CS-series, C200HX/
C200HG/C200HE-
(Z)E, and C200HS
Master Unit, CS-
series Master Unit,
or CJ-series Master
Unit
IN0 to IN7 and
OUT0 to OUT7
500
µ
s
4,000
µ
s
IN0 to IN15 and
OUT0 to OUT15
800
µ
s
6,000
µ
s
CQM1
IN0 to IN1 and
OUT0 to OUT1
500
µ
s
4,000
µ
s
IN0 to IN3 and
OUT0 to OUT3
IN0 to IN7 and
OUT0 to OUT7
Master
Input processing time
CS Series, C200HX/C200HG/C200HE-
(Z)E, and C200HS
160
µ
s
CQM1
120
µ
s
Usable node number setting
IN0 to IN7 and OUT0 to OUT7
IN0 to IN15 and OUT0 to OUT15
T
M-IN
= 100
µ
s
T
M-IN
= 130
µ
s
Usable node number setting
IN0 to IN7 and OUT0 to OUT7
IN0 to IN15 and OUT0 to OUT15
T
M-IN
= 100
µ
s
T
M-IN
= 130
µ
s
Master
Max. input processing time
CS Series, C200HX/C200HG/C200HE-
(Z)E, and C200HS
200
µ
s
CQM1
230
µ
s
Usable node number setting
IN0 to IN7 and OUT0 to OUT7
IN0 to IN15 and OUT0 to OUT15
T
M-out-max
= 130
µ
s
T
M-out-max
= 140