66
Master/Slave Connecting Cables
Section 3-4
Terminal-block
Terminators
When the VCTF cable is connected to an SRS1-T Terminal-block Terminator,
use crimp terminals on each of the BD H and BD L signal wires, and connect
them to each terminal. The signal wires can be connected to any of the termi-
nals.
Note
1.
Do not connect both signal wires to a single terminal.
2.
When connecting the communications power supply using Special Flat
Cable or 4-conductor VCTF cable, insulate the BD+ and BS– power supply
cables.
Tighten the terminal screws to the specified tightening torque (0.3 to
0.5 N
⋅
m).
3.
When connecting Terminal-block Terminators to VCTF cables, use the
same crimp terminals as those used to connect the communications ca-
bles to the Slaves. (Refer to
3-4 Master/Slave Connecting Cables.
)
Shield Terminators
When using 4-conductor VCTF cable, terminators can be connected by con-
necting an SRS2-1 Shield Terminator to the T-joint.
Note
The SRS2-1 Shield Connector has a male plug. Connect it to the female
socket connector of the T-joint.
3-4
Master/Slave Connecting Cables
This section describes the methods used for connecting communications
cables to each device and installing connectors on the Connector Terminal
and Sensor Terminal cables.
3-4-1
Crimp Terminal Installation
Attach crimp terminals to the ends of the communications cable when con-
necting the cable to a Master, Slave, Terminal-block Terminator, or commer-
cially available terminal block.
!Caution
Do not connect bare signal wires to the terminals since the wires could short
and damage the Unit to which they are connected.
Note
Do not strip too much insulation from the wires when preparing the cable for
the crimp terminals. Cover the shaft of the terminal connector and the end of
the wire with electrical tape or heat-shrinking tube.
Master or Slave
When connecting communications cable (VCTF cable or Special Flat Cable)
to a Master or Slave, attach an M3 crimp terminal like those shown below to
each signal wire.
M3 Terminals for the Master Unit (Except CJ Series)
Note
Refer to
4-3-3 Wiring and Installing Communications Cables
for details on
crimp terminals used for connecting CJ-series Master Units.
Recommended terminal
Comment
Nippon Crimp Terminal 1.25-N3A
Forked terminal
Molex Y1.25-3.5L
Forked terminal
6.2 mm max.
6.2 mm max.