52
Extended Speed and Acceleration Control IO (110/111)
APPENDIX B
Note
For safety reasons, the FWD, REV and RST command operation requires a
rising edge (0 to 1 transition) after power on and fault/trip reset.
Assembly ID 111:
Extended Speed and
Acceleration Control Input
Acceleration
time
Reference acceleration time. Unit: [0.1 s]
Range of setting [0.1 to 3600.0]
Be sure to set the REF bit to control the acceleration or deceleration
time using this assembly. Otherwise the F002 and F003 will be used
independent of parameter A001.
Deceleration
time
Reference deceleration time. Unit: [0.1 s]
Range of setting [0.1 to 3600.0]
Be sure to set the REF bit to control the acceleration or deceleration
time using this assembly. Otherwise the F002 and F003 will be used
independent of parameter A001.
Table B-25 Extended Speed and Acceleration Control Output - Assembly 110
Description (continued)
Name
Description
Table B-26 Extended Speed and Acceleration Control Input - Assembly 111
Allocation
Word
Byte
Bit Allocation
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
n
0
MI3
MI2
MI1
ARF
-
FLT
DRR
DFR
1
Drive status
n + 1
2
Rotational Speed Monitor (Low Byte)
3
Rotational Speed Monitor (High Byte)
n + 2
4
Output Current Monitor (Low Byte)
5
Output Current Monitor (High Byte)
n + 3
6
Trip Cause
7
RFN
CFN
-
-
MI7
MI6
MI5
MI4
Table B-27 Extended Speed and Acceleration Control Input - Assembly 111
Description
Name
Description
DFR
During forward run
0: Stop/reverse
1: During forward run
DRR
During reverse run
0: Stop/forward
1: During reverse run
FLT
Fault
0: Normal
1: Fault/trip
ARF
At reference
0: Acceleration or deceleration phase
1: At reference
MI1 to MI7
Monitor multi function inputs [1] to [7]
0: OFF
1: ON
CFN
Ctrl from net: run command input selection
0: Local
1: Devicenet reference
RFN
Ref from net: speed reference input selection
0: Local
1: Devicenet reference
Summary of Contents for 3G3AX-MX2-DRT-E
Page 6: ...vi...
Page 14: ...xiv Compliance with EC Directives...
Page 20: ...6 Introduction to DeviceNet Section 1 3...
Page 46: ...32 Monitoring additional Inverter status using COS Section 4 9...
Page 56: ...42 APPENDIX A...
Page 68: ...54 Extended Speed and Acceleration Control IO 110 111 APPENDIX B...
Page 84: ...70 AC DC Drive Object Class 0x2A APPENDIX D...