16
Configuring the Option Board
Section 3-2
Step 6
Inverter registers P044, P045 and P048 configure the DeviceNet network-
related parameters. Adjust these to configure required action in case a field-
bus network IDLE mode behaviour and/or a fieldbus failure occurs.
Step 7
Registers A001 and A002 are used by the Inverter to adjust the frequency
source and control source. If the second motor parameter set is used, regis-
ters A201 and A202 also have to be set. Adjust these in accordance with the
following table:
Step 8
Registers P033, P036, C021, C022 and C026 are used by the Inverter to
adjust some Inverter function sources. If required, adjust these in accordance
with the following table:
Table 10 Configuration of DeviceNet Parameters
Param
Description
Setting
P044
Network Error Timer
Communication watchdog timer while running.
Note
additional to DeviceNet inactivity / watchdog
timer.
0 to 9999 in 0.1 s unit. Set to 0 to disable.
P045
Action on Network
Error
Set to 0 for inverter trip (Default)
Set to 1 for deceleration and trip
Set to 2 for no action
Set to 3 for stop due to free-run
Set to 4 for deceleration and stop
P048
Action on Network
Idle Mode
Set to 0 for inverter trip (Default)
Set to 1 for deceleration and trip
Set to 2 for no action
Set to 3 for stop due to free-run
Set to 4 for deceleration and stop
Table 11 Configuration of Source Selection Parameters
Param
Description
Setting
A001
Motor 1
Frequency Source
For option board as source:
Set to 4 "Option Board input" for all assemblies
except Flexible format (P046 is not 6)
Set to 3 "Modbus network input" in case of Flexible
format (P046 is 6)
A002
Motor 1 Run
Command Source
Table 12 Configuration of Other Selection Parameter
Param
Description
Setting
P033
Torque Command
Source
For option board as source:
Set to 6 "Option Board input" for all assemblies
except Flexible format (P046 is not 6)
Set to 3 "Digital Operator input" for Flexible format
(P046 is 6)
P036
Torque Bias Mode
For option board as source:
Set to 5 "Option Board input" for all assemblies
except Flexible format (P046 is not 6)
Set to 3 "Digital Operator input" for Flexible format
(P046 is 6)
C021
Output Terminal 11
Source
Set to 63 for option board as source
C022
Output Terminal 12
Source
Set to 63 for option board as source
C026
Alarm Relay Source
Set to 63 for option board as source (optional)
Summary of Contents for 3G3AX-MX2-DRT-E
Page 6: ...vi...
Page 14: ...xiv Compliance with EC Directives...
Page 20: ...6 Introduction to DeviceNet Section 1 3...
Page 46: ...32 Monitoring additional Inverter status using COS Section 4 9...
Page 56: ...42 APPENDIX A...
Page 68: ...54 Extended Speed and Acceleration Control IO 110 111 APPENDIX B...
Page 84: ...70 AC DC Drive Object Class 0x2A APPENDIX D...