Troubleshooting Using the LED Indicators
Section 5-1
The Option Board encountered a fatal
error during Power-on
Check that the Option Board is mounted properly and restart
the Option Board. If the problem persists, replace the Option
Board.
The Inverter does not support a 3G3AX-
MX2-DRT-E (Refer to section
5-1-2 Con-
figuration Errors
)
Replace the Inverter with a later version.
The Option Board connector is damaged
Replace the Option Board.
The Option Board encountered a fatal
error during Operation.
Check that the option is mounted properly and restart the Option
Board. If the problem persists, replace the Option Board
The Inverter is tripped with the Force
external Fault/Trip through the fieldbus.
Clear the FFL Force external fault bit and reset the trip.
The Inverter detected a fatal error in the
operation of the Option Board.
Check that the option is mounted properly and restart the
Option Board. If the problem persists, replace the Option Board
Table 24 Option Board or Inverter Errors
Display &
Indicators
Possible Cause(s)
Corrective Action
MS
NS
MS
NS
MS NS
MS NS