Extended Speed and Torque Control IO (123/173)
APPENDIX B
B-3
Extended Speed and Torque Control IO (123/173)
Assembly ID 123:
Extended Speed and
Torque Control Output
RDY
Inverter ready status
0: Inverter not ready
1: Inverter ready
CFN
Ctrl from net: run command input selection
0: Local
1: Devicenet reference
RFN
Ref from net: speed reference input selection
0: Local
1: Devicenet reference
ARF
At reference
0: Acceleration or deceleration phase
1: At reference
Drive Status
Drive Status
1: Startup
2: Not ready
3: Ready
4: Enabled
5: Stopping
6: Fault / trip stop
7: Faulted / tripped
Rotational
Speed Monitor
Actual rotational speed monitor. Unit: [RPM]/[0.1 Hz]/[0.01 Hz].
If Motor poles setting for RPM (inverter parameter P049 is set to
zero, the Unit depends on the inverter mode (d060):
d060 = 2 (High Frequency mode): Unit is [0.1 Hz]
d060 != 2 (High Frequency mode): Unit is [0.01 Hz]
Table B-8
Extended Speed Control Input - Assembly 71 Description (continued)
Name
Description
Table B-9
Extended Speed and Torque Control Output - Assembly 123 Allocation
Word
Byte
Bit Allocation
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
n
0
-
REF
CTR
-
-
RST
REV
FWD
1
-
-
-
-
-
-
-
-
n + 1
2
Rotational Speed Reference (Low Byte)
3
Rotational Speed Reference (High Byte)
n + 2
4
Torque Reference (Low Byte)
5
Torque Reference (High Byte)
Table B-10 Extended Speed and Torque Control Output - Assembly 123 Description
Name
Description
FWD
Forward run command
0: Stop
1: Forward run
REV
Reverse run command
0: Stop
1: Reverse run
RST
Fault reset
Reset fault / trip condition on transition from 0 to 1
CTR
NetCtrl run command selection
0: Setting of inverter parameter A002
1: Network controlled
REF
NetRef speed reference selection
0: Setting of inverter parameter A001
1: Network controlled
Summary of Contents for 3G3AX-MX2-DRT-E
Page 6: ...vi...
Page 14: ...xiv Compliance with EC Directives...
Page 20: ...6 Introduction to DeviceNet Section 1 3...
Page 46: ...32 Monitoring additional Inverter status using COS Section 4 9...
Page 56: ...42 APPENDIX A...
Page 68: ...54 Extended Speed and Acceleration Control IO 110 111 APPENDIX B...
Page 84: ...70 AC DC Drive Object Class 0x2A APPENDIX D...