15
SECTION 3
Configuring Drive Parameters and Option Board
3-1
Installation of EDS files
For each of the MX2 Inverter models, a specific EDS file exists for the Option
Board. The EDS files contain specific parameter data (default, ranges)
depending on the model. Perform the following steps to install the EDS files
prior to configure the network.
Step 1
Download the EDS files named
3G3AX-MX2-DRT-
@
-E.eds
for the
3G3AX-MX2-DRT-E Option Board via the Omron website (http://
industrial.omron.eu).
Step 2
Install / add these EDS files to the DeviceNet Master Unit configuration pro-
gram used to configure your DeviceNet master.
3-2
Configuring the Option Board
All Option Board parameters are stored in the MX2-A
@
Inverter. This allows
for easy replacement of the Option Board without the need to re-configure.
After connecting the Option Board to an MX2-A
@
Inverter for the first time
however, proceed with the following steps:
Step 3
Set the DeviceNet node number / MAC ID by configuring inverter parameter
P192. Use either the Inverter keypad or any other method of configuring the
inverter parameters. See note 1.
Step 4
When using the automatic / fixed allocation mechanism of the DeviceNet Mas-
ter Unit (see next section), choose the required Output and Input assembly
pair using inverter parameter P046 Default Connection Path.
Step 5
It is recommended to set C102 = 3 to prevent the Inverter reset input and
Stop/reset button from interfering with Option Board during operation. Setting
C102 to another value causes the Option Board to reset when a trip condition
is cleared. See the MX2 User’s manual (Cat. No. I570) for details on this
parameter.
Table 7 Configuration of Node Number
Param
Description
Setting
P192
DeviceNet Node
Address
0 to 63 (default: 63)
Table 8 Default Connection Path
P046
value
Description
Assembly nr (Hex)
Output
Input
0
Basic Speed IO
20
70
1
Extended Speed IO (default)
21
71
2
Extended Speed and Torque Control
123
173
3
Special IO
100
150
4
Extended Control IO
101
151
5
Extended Control IO and Multi Function IO Monitor
101
153
6
Flexible Format
139
159
7
Extended Speed and Acceleration Control
110
111
Table 9 Configuration of Inverter Reset Mode Selection
Param
Description
Setting
C102
Reset mode selection Set to 3 "Resetting only trip" (recommended setting)
Summary of Contents for 3G3AX-MX2-DRT-E
Page 6: ...vi...
Page 14: ...xiv Compliance with EC Directives...
Page 20: ...6 Introduction to DeviceNet Section 1 3...
Page 46: ...32 Monitoring additional Inverter status using COS Section 4 9...
Page 56: ...42 APPENDIX A...
Page 68: ...54 Extended Speed and Acceleration Control IO 110 111 APPENDIX B...
Page 84: ...70 AC DC Drive Object Class 0x2A APPENDIX D...