65
APPENDIX D
AC Drive Object Specification
D-1
Motor Data Object (Class 0x28)
Supported Service Codes
Table D-1 Motor Data Object - Supported Service Codes
Object Details
Note
A change of the Motor Type value will cause an inverter and DeviceNet option
board reset. This is equivalent to setting inverter parameters b171 (Inverter
mode selection) and b180 (Parameter initialisation trigger).
Service Code No. (hex)
Service
0E
Get attribute single
10
Set attribute single
Table D-2 Motor Data Object - Object Details
Instance
(hex)
Attribute
(hex)
Name
Content
Setting
range
Default
Get
Set
Size
01
03
Motor Type
Depends on the motor control mode which is
selected for the inverter. The motor control mode
can be read by inverter parameter d060.
Get values:
3: PM synchronous motor (d060 = 3)
7: Squirrel cage induction motor (d060 != 3)
Set values:
3: in case inverter control mode is not in this mode,
the inverter will be set to PM synchronous mode
(d060 = 3).
7: in case inverter control mode is PM synchronous
mode (d060 = 3), the inverter will be set to ND
mode (d060 = 1).
See note
----
7
Yes
Yes
US
INT
06
Rated Current
Motor rated current. Unit: [0.1 A]
----
Depend-
ing on
inverter
type
Yes
Yes
UINT
07
Rated Voltage
Motor rated voltage. Unit: [V]
Set: Only defined set of values as indicated for
inverter parameter A082 (AVR voltage select) are
accepted.
----
Depend-
ing on
inverter
type
Yes
Yes
UINT
08
Rated Power
Motor rated power. Unit: [W]
Set: Only defined set of values as indicated for
inverter parameter H003 (Squirrel cage induction
motor) or H103 (PM Synchronous mode) are
accepted.
----
Depend-
ing on
inverter
type
Yes
Yes
UINT
09
Rated Frequency Motor rated frequency. Unit: [Hz].
300 - MaxSpeed 50
Yes
Yes
UINT
11
MaxSpeed
Maximum allowed motor speed. Unit: [RPM]
Depending on
motor control
mode
50
Yes
Yes
UINT
12
PoleCount
Number of poles in the motor.
(speed conversion only)
Only even number of poles are valid.
0 - 38
0
Yes
Yes
UINT
Summary of Contents for 3G3AX-MX2-DRT-E
Page 6: ...vi...
Page 14: ...xiv Compliance with EC Directives...
Page 20: ...6 Introduction to DeviceNet Section 1 3...
Page 46: ...32 Monitoring additional Inverter status using COS Section 4 9...
Page 56: ...42 APPENDIX A...
Page 68: ...54 Extended Speed and Acceleration Control IO 110 111 APPENDIX B...
Page 84: ...70 AC DC Drive Object Class 0x2A APPENDIX D...