![background image](http://html1.mh-extra.com/html/omron/3g3ax-mx2-drt-e/3g3ax-mx2-drt-e_user-manual_740780091.webp)
77
Explicit Message Error Codes
APPENDIX E
E-4
Explicit Message Error Codes
When an error response has been returned for the executed explicit message,
this response will have the following format.
Within the frame, one of the following error codes will be included.
Table E-5 Error Response
Response
Code
Error Name
Cause
02
@@
Resource unavailable
An internal communication error between
Option Board and Inverter
08
@@
Service not supported
The service code is incorrect.
09
@@
Invalid attribute value
The specified attribute / inverter parame-
ter value is not supported. The data writ-
ten is outside range.
0C
@@
Object state conflict
The specified command cannot be exe-
cuted due to an internal error.
0E
@@
Attribute not settable
An attribute ID supported only for reading
has been executed for a write service
code.
10
@@
Device state conflict
The specified command cannot be exe-
cuted in this inverter mode.
13
@@
Not enough data
The data is smaller than the specified
size (accessing only high word of double
word).
14
@@
Attribute not supported
The attribute or inverter parameter does
not exists.
15
@@
Too much data
The data is larger than the specified size
(accessing single word with double word
data).
16
@@
Object does not exist
The specified Instance ID is not sup-
ported.
1F
@@
Vendor specific
This code is returned in case of an
Inverter error.
20
@@
Invalid parameter
The specified operation command data is
not supported.
Source node address
04
94
Error Code
Service code
No. of bytes received
Summary of Contents for 3G3AX-MX2-DRT-E
Page 6: ...vi...
Page 14: ...xiv Compliance with EC Directives...
Page 20: ...6 Introduction to DeviceNet Section 1 3...
Page 46: ...32 Monitoring additional Inverter status using COS Section 4 9...
Page 56: ...42 APPENDIX A...
Page 68: ...54 Extended Speed and Acceleration Control IO 110 111 APPENDIX B...
Page 84: ...70 AC DC Drive Object Class 0x2A APPENDIX D...