Basic Format of Explicit Messages
APPENDIX E
Response:
The latest trip of the inverter has been caused by E62 (value 3E Hex). This is
Force fault/trip from the option board.
Example 3:
Writing BOOL Object
ForceFault/Trip
Parameter:Class 29 Hex, Instance 01 Hex, Attribute 11 Hex
Command:
Response:
Example 4:
Read INT SpeedActual
Parameter:Class 2A Hex, Instance 01 Hex, Attribute 07 Hex
Command:
Response:
The actual speed is read as 10.0 Hz (0064 Hex). Please note the swapping of
the data following CIP data type encoding.
No. of bytes received
3E
Data
Service code
Source node address
03
8E
Instance ID
10
01
Attribute ID
Data
29
01
11
Class ID
Service code
Destination node address
90
Service code
Source node address
No. of bytes received
02
Instance ID
Class ID
2A
01
07
Attribute ID
Service code
Destination node address
0E
Service code
Data
64
00
Source node address
No. of bytes received
04
8E