Option Board Specifications
Section 1-2
1-2
Option Board Specifications
Note 1
The derated- or ambient operating temperature of the MX2 Inverter takes pre-
cedence over that of the Option Board.
Note 2
In case the 3G3AX-MX2-DRT-E is connected to the MX2-A
@
Inverter, it is not
supported to connect any external devices to the RS485 (Modbus) interface
and the RJ45 port (Optional operator port) of the inverter.
Table 1 Option Board Specification
Item
Specification
Installation
Unit type
MX2 Series Option Board
Model
3G3AX-MX2-DRT-E
Dimensions (W x H x D)
68 x 58 x 45 mm
Weight
170g (typical)
Environment
Ambient operating temperature
-10 to 55°C (no icing or condensation)
Ambient operating humidity
20 to 90%RH
Ambient storage temperature
-20 to 65°C (no icing or condensation)
Vibration resistance
5.9m/s2 (0.6G) at 10…55Hz
Dielectric strength
500 VAC (between isolated circuits)
Conformance to EMC and Electri-
cal safety standards
EN61800-3: 2004 (2004/108/EC) Second environment, Category
C3
EN61800-5-1: 2007 (2006/95/EC) SELV
Enclosure rating
IP 20
DeviceNet
Interface
Communications protocol
DeviceNet
Certification
DeviceNet Conformance Tested
DeviceNet Profile
AC Drive (0x02)
Supported connections
Remote I/O: Master-Slave connection
Poll
Bit-Strobe
COS
Cyclic
Explicit Messages
Conform to DeviceNet specifications
Communications power supply
11 to 25 VDC
Unit device address range
MAC ID 0 to 63, set with inverter parameter P192
Baud rates supported
125, 250 or 500 kbps. Automatically detecting baud rate of Master
Unit
DeviceNet
Configuration
Default Connection path
Supported, set with inverter parameter P046
Supported Assemblies
Basic Remote IO (Output assembly 20, Input assembly 70)
Extended Speed IO (21, 71)
Extended Speed and Torque Control (123, 173)
Special IO (100, 150)
Extended Control IO (101, 151)
Extended Control IO and Multi function IO monitor (101, 153)
Flexible Format (139, 159)
Extended Speed and Acceleration Control (110, 111)
In case the DeviceNet master is configured using user allocation,
only the input / output pairs can be configured.
EDS file
Depending on the MX2-A
@
inverter model (see below)
Summary of Contents for 3G3AX-MX2-DRT-E
Page 6: ...vi...
Page 14: ...xiv Compliance with EC Directives...
Page 20: ...6 Introduction to DeviceNet Section 1 3...
Page 46: ...32 Monitoring additional Inverter status using COS Section 4 9...
Page 56: ...42 APPENDIX A...
Page 68: ...54 Extended Speed and Acceleration Control IO 110 111 APPENDIX B...
Page 84: ...70 AC DC Drive Object Class 0x2A APPENDIX D...