Enable only when 'Emergency stop' is selected from the multi-function options.
Error name
Display
Details
Operation
when error is
detected
Recovery
method
Free-run stop
input
(Flashing)
Include free-run stop/error reset input.
Free-run stop
Canceling the
free-run stop
input.
Emergency
stop input
(Flashing)
Include emergency stop/error reset input. *3
Canceling the
emergency stop
input.
System error
A communication with the operator is not
established within 7 seconds after applying the
power.
Local:
Free-run stop
Remote:
Continuous
operation
If the fault is not
eliminated even
after applying the
power again,
inform us.
A communication with the operator is not
established within 7 seconds after initiating the
communication.
Detected disconnection or short circuit of the
thermistor used for detecting the temperature.
Free-run stop
Detected an error in the EEPROM used for
storing the constants and error history.
Detected an error in the CPU with built-in A/D
conversion circuit.
Detected an error in the current detector circuit.
Detected an error in the hardware ID circuit.