
82
Digitax HD M753 Control User Guide
Issue Number: 3
8.1.3
Open loop motor control
Pr 00.046 {05.007}
Rated Current
Defines the maximum continuous motor current
The motor rated current parameter must be set to the maximum continuous current of the motor. The motor rated current is used in the following:
•
Current limits (see section 8.2
on page 92, for more information)
•
Motor thermal overload protection (see section 8.3
on page 92, for more information)
•
Vector mode voltage control (see
Open Loop Control Mode
(00.007), later in this table)
•
Slip compensation (see
Enable Slip Compensation
(05.027), later in this table)
•
Dynamic V/F control
Pr 00.044 {05.009}
Rated Voltage
Defines the voltage applied to the motor at rated frequency
Pr 00.047 {05.006}
Rated Frequency
Defines the frequency at which rated voltage is applied
The
Rated Voltage
(00.044) and the
Rated Frequency
(00.047) are used to
define the voltage to frequency characteristic applied to the motor (see
Open
Loop Control Mode
(00.007), later in this table). The
Rated Frequency
(00.047) is also used in conjunction with the motor rated speed to calculate
the rated slip for slip compensation (see
Rated Speed
(00.045), later in this
table).
Pr 00.045 {05.008}
Rated Speed
Defines the full load rated speed of the motor
Pr 00.042 {05.011}
Number Of Motor Poles
Defines the number of motor poles
The motor rated speed and the number of poles are used with the motor rated frequency to calculate the rated slip of induction machines in Hz.
Rated slip (Hz) = Motor rated frequency - (Number of pole pairs x [Motor rated speed / 60]) =
If Pr
00.045
is set to 0 or to synchronous speed, slip compensation is disabled. If slip compensation is required this parameter should be set to the nameplate
value, which should give the correct rpm for a hot machine. Sometimes it will be necessary to adjust this when the drive is commissioned because the
nameplate value may be inaccurate. Slip compensation will operate correctly both below base speed and within the field-weakening region. Slip
compensation is normally used to correct for the motor speed to prevent speed variation with load. The rated load rpm can be set higher than synchronous
speed to deliberately introduce speed droop. This can be useful to aid load sharing with mechanically coupled motors.
Pr
00.042
is also used in the calculation of the motor speed display by the drive for a given output frequency. When Pr
00.042
is set to ‘Automatic’, the
number of motor poles is automatically calculated from the rated frequency Pr
00.047
, and the motor rated speed Pr
00.045
.
Number of poles = 120 x (
Rated Frequency
(00.047) /
Rated Speed
(00.045)) rounded to the nearest even number.
Pr 00.043 {05.010}
Rated Power Factor
Defines the angle between the motor voltage and current
The power factor is the true power factor of the motor, i.e. the angle between the motor voltage and current. The power factor is used in conjunction with the
Rated Current
(00.046), to calculate the rated active current and magnetising current of the motor. The rated active current is used extensively to control the
drive, and the magnetising current is used in vector mode stator resistance compensation. It is important that this parameter is set up correctly. The drive can
measure the motor rated power factor by performing a rotating autotune (see Autotune (Pr 00.040), overleaf).
Pr 00.040 {05.012}
Autotune
There are two autotune tests available in open loop mode, a stationary and a rotating test. A rotating autotune should be used whenever possible so the
measured value of power factor of the motor is used by the drive.
•
A stationary autotune can be used when the motor is loaded and it is not possible to remove the load from the motor shaft. The stationary test measures
the
Stator Resistance
(05.017),
Transient Inductance
(05.024),
Maximum Deadtime Compensation
(05.059) and
Current At Maximum Deadtime
Compensation
(05.060) which are required for good performance in vector control modes (see
Open Loop Control Mode
(00.007), later in this table). The
stationary autotune does not measure the power factor of the motor so the value on the motor nameplate must be entered into Pr
00.043
. To perform a
Stationary autotune, set Pr
00.040
to 1, and provide the drive with both an enable signal (terminal 2 & 6) and a run signal (terminal 11 or 13).
•
A rotating autotune should only be used if the motor is unloaded. A rotating autotune first performs a stationary autotune, as above, then a rotating test is
performed in which the motor is accelerated with currently selected ramps up to a frequency of
Rated Frequency
(05.006) x 2/3, and the frequency is
maintained at that level for 4 seconds.
Stator Inductance
(05.025) is measured and this value is used in conjunction with other motor parameters to
calculate
Rated Power Factor
(05.010). To perform a Rotating autotune, set Pr
00.040
to 2, and provide the drive with both an enable signal (terminal 2 &
6) and a run signal (terminal 11 or 13).
Following the completion of an autotune test the drive will go into the inhibit state. The drive must be placed into a controlled disable condition before the drive
can be made to run at the required reference. The drive can be put in to a controlled disable condition by removing the Safe Torque Off signal from terminal 2
& 6, setting the
Drive Enable
(06.015) to OFF (0) or disabling the drive via the
Control Word
(06.042) and
Control Word Enable
(06.043).
Output
voltage
Pr
/ 2
00.044
Pr
00.044
Pr
/ 2
00.047
Pr
00.047
Output
frequency
Output voltage characteristic
00.047
00.042
2
------------------
00.045
60
------------------
=
Summary of Contents for Digitax HD M753 EtherCAT
Page 261: ......
Page 262: ...0478 0461 03...