234
Digitax HD M753 Control User Guide
Issue Number: 3
External Trip
An External trip is initiated
6
An
External Trip
has occurred. The cause of the trip can be identified from the sub trip number displayed after the trip string.
See table below. An external trip can also be initiated by writing a value of 6 in Pr
10.038
.
Recommended actions:
•
Check the Safe Torque Off signal voltage (on terminals 2 & 6) equals to 24 V.
•
Check the value of Pr
08.009
which indicates the digital state of terminals 2 & 6, equates to ‘on’.
•
If external trip detection of the Safe Torque Off input is not required, set Pr
08.010
to OFF (0).
•
Check the value of Pr
10.032
.
•
Select ‘Destinations’ (or enter 12001) in Pr
mm.000
and check for a parameter controlling Pr
10.032
.
•
Ensure Pr
10.032
or Pr
10.038
(= 6) is not being controlled by serial comms
HF01
Data processing error: CPU address error
The
HF01
trip indicates that a CPU address error has occurred. This trip indicates that the control PCB on the drive has
failed.
Recommended actions:
•
Hardware fault – Contact the supplier of the drive
HF02
Data processing error: DMAC address error
The
HF02
trip indicates that a DMAC address error has occurred. This trip indicates that the control PCB on the drive has
failed.
Recommended actions:
•
Hardware fault – Contact the supplier of the drive
HF03
Data processing error: Illegal instruction
The
HF03
trip indicates that an illegal instruction has occurred. This trip indicates that the control PCB on the drive has
failed.
Recommended actions:
•
Hardware fault – Contact the supplier of the drive
HF04
Data processing error: Illegal slot instruction
The
HF04
trip indicates that an illegal slot instruction has occurred.This trip indicates that the control PCB on the drive has
failed.
Recommended actions:
•
Hardware fault – Contact the supplier of the drive
HF05
Data processing error: Undefined exception
The
HF05
trip indicates that an undefined exception error has occurred. This trip indicates that the control PCB on the drive
has failed.
Recommended actions:
•
Hardware fault – Contact the supplier of the drive
HF06
Data processing error: Reserved exception
The
HF06
trip indicates that a reserved exception error has occurred. This trip indicates that the control PCB on the drive
has failed.
Recommended actions:
•
Hardware fault – Contact the supplier of the drive
HF07
Data processing error: Watchdog failure
The
HF07
trip indicates that a watchdog failure has occurred. This trip indicates that the control PCB on the drive has failed.
Recommended actions:
•
Hardware fault – Contact the supplier of the drive
HF08
Data processing error: CPU Interrupt crash
The
HF08
trip indicates that a CPU interrupt crash has occurred. This trip indicates that the control PCB on the drive has
failed.
Recommended actions:
•
Hardware fault – Contact the supplier of the drive
Trip
Diagnosis
Sub-trip
Reason
1
External Trip Mode
(08.010) = 1 or 3 and Safe Torque Off input 1 is low
2
External Trip Mode
(08.010) = 2 or 3 and Safe Torque Off input 2 is low
3
External Trip
(10.032) = 1