Installing the Base Station Equipment
WiLink-I Modular Base Station System Manual
43
GPS/SYNC IN
15-pin micro D-Type jack
Not used currently. Connection to a GPS receiver or to an
NPU in another chassis that supplies synchronization
signals
GPS/SYNC OUT
15-pin micro D-Type jack
Not used currently. Supply of synchronization signals to
another unit
ALRM-IN
9-pin micro D-Type jack
Not used currently. Connections to external alarm indicators
(3 alarm inputs, NC or NO)
ALRM-OUT
9-pin micro D-Type jack
Not used currently. Connections for activation of external
devices (4 dry contact pairs)
MON
3-pin low profile jack
Access for debugging and configuration using the Monitor
program
Table 2-13: NPU LEDs
Name
Description
Functionality
PWR
Power indication
¢
Off - NPU is not powered
¢
Red - NPU power failure
¢
Green - NPU power is OK
ALRM
NPU Alarm indication
¢
Off - NPU is OK
¢
Red - NPU failure
BST ALRM
Base Station chassis alarm
indication
¢
Off - All Base Station modules are OK
¢
Red - Failure in one (or more) Base Station modules
EXT ALRM
External alarm indication
¢
Off - No alarms
¢
Red - Alarm received via the ALRM IN connector
MASTER
Master/Slave operation indication
¢
Off - Secondary NPU (backup)
¢
Green - Primary NPU
GPS/SYNC
GPS/IF clock synchronization
functionality indication
¢
Off - GPS/IF clock synchronization is disabled
¢
Green - GPS/IF clock is synchronization enabled
Table 2-12: NPU Connectors
Name
Connector
Functionality