ioLogik E2200 Series
Using ioAdmin
3-33
Active Tags Tab
When logged in as administrator, fill in the fixed IP address on the
Active Tags
panel to configure the Active
OPC Address and Port settings. The Active OPC Server Address can be filled in using the IP or DNS format. The
default port number is 9900. The port number should be the same as the setting in Active OPC Server’s “Active
Tag Listen Port.” After the OPC setting and Channel Tags have been configured, click
Create Tags
. The ioLogik
E2200 must be rebooted in order for the settings to take effect.
ioLogik E2240
ioLogik E2210
The Heartbeat Interval can be used to determine the connection status between the ioLogik and Active OPC
Server, and to ensure that the ioLogik is connected and alive. Set the heartbeat interval to “0” to disable the
heartbeat. When the heartbeat is disabled, the SysConnect tag on the Active OPC Server will always be 1,
which means that the Active OPC Server will not be notified if a remote ioLogik is disconnected from the
network. If the heartbeat interval is set and the network between the ioLogik and Active OPC Server is down,
Active OPC Server will detect the stopped heartbeat and the Quality column in the Active OPC will display BAD
to indicate the loss of connectivity