ioLogik E2200 Series
Using ioAdmin
3-24
You can control how a DO/Relay output channel acts when the network is disconnected by using the
Safe
Status Settings
and the
Host Connection Watchdog
. When the
Host Connection Watchdog
is enabled,
a network disconnection will activate the
Safe Status Settings
. The DO channel can be configured to turn on,
turn off, or commence pulse output. If the
Host Connection Watchdog
is not enabled, then the DO/Relay
Output channel status will remain unchanged during a network disconnection.
ATTENTION
The Host Connection Watchdog is disabled by default and must be enabled for Safe Status Settings to take
effect.
Alias Name Configuration
Alias Name
helps users configure the alias of a DI or DO channels and define the logic level (0 or 1) for the
ON/OFF status. The Alias can be monitored by the ioAdmin utility, or can be queried using a user-defined
program based on the Moxa MXIO library, or a standard Modbus/TCP protocol.