ioLogik E2200 Series
Using ioAdmin
3-18
The
Reset Min
and
Reset Max
buttons will clear the minimum or maximum values recorded and displayed in
the ioAdmin main window.
Configuring Analog Output Channels
The ioLogik device’s analog output (AO) range can be set to either 0–10 V or 4–20 mA. You may also configure
all channels at the same time by selecting the
Apply to all channels
checkbox.
Power On Settings
:
Use this field to set the initial value for the AO channel when the ioLogik E2240 is
powered on. The
Power On Settings
field uses raw data values. If you do not know how to translate the raw
data values into real values, use the
Test
function for assistance.
Safe Status Settings
: Use this field to specify how the AO channel responds to a break in network
communication. When the network connection is lost for the amount of time specified in the Host Connection
Watchdog, the ioLogik E2240 enters Safe Status, and the AO channel’s Safe Status settings will go into effect.
Note that the Host Connection Watchdog is disabled by default. If the Host Connection Watchdog is disabled,
the ioLogik E2240 will never enter Safe Status and the Safe Status settings will have no effect.