ioLogik products are embedded with various types of I/O channels, and the mode of each input/output channel
must be configured before using the channels. Channels are divided into four categories: digital inputs, digital
outputs, analog inputs, and analog outputs.
Digital Input Mode Selection
A DI channel can be set to
DI
or
Event Counter
mode. In DI mode, the channel connects to wet/dry contacts.
In Event Counter mode, the channel accepts limit or proximity switches and counts events according to the
ON/OFF status. When “Lo to Hi” is selected, the counter value increases when the attached switch is pushed.
When “Hi to Lo” is selected, the counter value increases when the switch is pushed and released.
When logged in as administrator, double click on a channel in the
I/O Configuration
panel to configure that
channel’s settings. A window will open with configuration options for that channel. Each DI channel will be
configured to act as either a DI or Event Counter channel, according to the
Mode Settings
. To switch between
DI and Event Counter channel operation, select the desired mode in under
Mode Settings.
ATTENTION
On this panel, be sure to select
Start
under “Counter mode parameter” on “Power On Settings” to activate the
Event Counter channel.
Summary of Contents for ioLogik E2210
Page 138: ...ioLogik E2200 Series Cable Wiring D 4 Digital Output Sink Type...
Page 139: ...ioLogik E2200 Series Cable Wiring D 5 RTD Input Wiring Structure 2 wire 3 wire...
Page 140: ...ioLogik E2200 Series Cable Wiring D 6 Thermocouple Input Wiring Structure 2 wire...
Page 144: ...ioLogik E2200 Series Input and Output Terminal E 4 ioLogik E2262 I O left to right...