ioLogik E2200 Series
Introduction
1-7
ioLogik E2214 Specifications
Inputs and Outputs
Digital Inputs:
6 channels
Relay Outputs:
6 channels
Isolation:
3K VDC or 2K Vrms
Digital Input
Sensor Type:
Wet Contact (NPN or PNP) and Dry Contact
I/O Mode:
DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact(DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
Common Type:
3 points per COM
Counter Frequency:
900 Hz, power off storage
Digital Filtering Time Interval:
Software selectable
Relay Output
Type:
Form A (N.O.) power relay
Contact Current Rating:
• Inductive Load: 2 A @ 30 VDC, 250 VAC, 110 VAC
• Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC
Minimum permitted load:
1 A @ 5 VDC
Initial Insulation Resistance:
1000 M ohms (min.) @ 500 VDC
Mechanical endurance:
1,000,000 operations
Electrical endurance: 100,000 operations @ 5 A resistive load
Contact Resistance:
100 m ohms (max.)
Pulse Output:
0.3 Hz at rated load
Power Requirements
Power Consumption:
170 mA @ 24 VDC
MTBF
(mean time between failure)
Time:
307,239 hrs
Database:
Telcordia (Bellcore)
Summary of Contents for ioLogik E2210
Page 138: ...ioLogik E2200 Series Cable Wiring D 4 Digital Output Sink Type...
Page 139: ...ioLogik E2200 Series Cable Wiring D 5 RTD Input Wiring Structure 2 wire 3 wire...
Page 140: ...ioLogik E2200 Series Cable Wiring D 6 Thermocouple Input Wiring Structure 2 wire...
Page 144: ...ioLogik E2200 Series Input and Output Terminal E 4 ioLogik E2262 I O left to right...