ioLogik E2200 Series
Using ioAdmin
3-21
Configuring Digital Input Channels
The ioLogik E2210 can support up to 12 digital input (DI) channels. Software filtering is used to control switch
bounces. Under
1. Mode Settings
, the
Filter
field is configurable in multiples of 0.5 ms and accepts values
between 1 and 65535. For example, a setting of
100
would mean a 50 ms filter (100 × 0.5 ms).
A DI channel can be set to “DI” or “Event Counter” mode. In DI mode, the specifications are as follows:
Type
ON
OFF
Dry contact
Short to GND
Open
Wet contact
0 to 3 VDC
10 to 30 VDC
In
Event Counter mode
, the channel accepts limit or proximity switches and counts events according to the
ON/OFF status. When
Lo to Hi
is selected, the counter value increases when the attached switch is pushed.
When
Hi to Lo
is selected, the counter value increases when the switch is released. When
Both
is selected, the
counter value increases when the attached switch is pushed or released.