ioLogik E2200 Series
Using ioAdmin
3-35
Active Tags
A tag selection table shown in the right panel of the browser window shows the details of your selection.
The I/O status of a channel can be updated to the Active OPC Server once it is changed, or updated periodically.
1.
Checkmark the “On Change” setting to force an update when there is a signal change for that channel (On
to Off or Off to On for digital channels, or percentage change for analog channels).
2.
To periodically update the status of the Active OPC Server, specify a time interval after the "Update per:"
checkbox.
NOTE
If AI is configured to update
on change
, the percentage settings represents the percentage of the full analog
range. For example, if the AI is configured to 0 to 10V,
On Change 1%
means the ioLogik will update the
Active OPC Server every time there is 0.1 V change.
Refer to the
Active OPC Server
section for more details about how to use Active OPC Server.