ioLogik E2200 Series
Using the Web Console
5-6
In Event Counter mode, the channel accepts limit or proximity switches and counts events according to the
ON/OFF status. When “Lo to Hi” is selected, the counter value increases when the attached switch is pushed.
When “Hi to Lo” is selected, the counter value increases when the switch is pushed and released.
By default, the Event Counter value will be reset to zero if power is disconnected. If you select
Save Status on
Power Failure
, the Event Counter value will be saved when power is disconnected. When power is
reconnected, the value will be as you left it. You can set
Power On Setting
to have counting resume
immediately.
DI channels that are in Event Counter mode can begin counting automatically when the ioLogik is powered on.
To activate this function, enable
Power On Setting.
If
Power On Setting
is not enabled, the channel will only
start counting events when specified by a Modbus command or Click&Go Logic rule.
You can control how an Event Counter channel behaves during a network disconnection with the
Safe Status
Setting
and the
Host Connection Watchdog
. With the Watchdog disabled, the Event Counter continues
counting events even when there is a network disconnection. With the Watchdog enabled, the
Safe Status
Setting
specifies whether the Event Counter continues or suspends counting when there is a network
disconnection. Counting will continue if
Safe Status Setting
is enabled; counting will be suspended if
Safe
Status Setting
is not enabled.
NOTE
The ioLogik E2210 does not support the Save Status function in the event of a power failure.
DO Channels
On the
DO Channels
page, you can view the status of each DO (digital output) channel. Only DIO channels
that are acting as DO channels will be displayed.
Summary of Contents for ioLogik E2210
Page 138: ...ioLogik E2200 Series Cable Wiring D 4 Digital Output Sink Type...
Page 139: ...ioLogik E2200 Series Cable Wiring D 5 RTD Input Wiring Structure 2 wire 3 wire...
Page 140: ...ioLogik E2200 Series Cable Wiring D 6 Thermocouple Input Wiring Structure 2 wire...
Page 144: ...ioLogik E2200 Series Input and Output Terminal E 4 ioLogik E2262 I O left to right...