A953 HANDY GOT
Computer Link Connection 7
7-2
7.2
Initial setting
7.2.1
Setting in communication link unit and serial communication unit
When connecting the GOT to a computer link unit or serial communication unit for monitoring,
set the switches of the computer link unit or the serial communication unit as shown below.
1) When the QJ71C24(-R2) is connected
Set the switches of the QJ71C24(-R2) using the I/O assignment setting of the GPPW. For
the details of the setting method, refer to the GPPW OPERATING MANUAL.
The contents of setting vary depending on the CH (interface number) of the serial
communication unit connected to the GOT.
Set the switches in accordance with the connected CH as follows.
Point
When the GOT is connected, the CH1 and the CH2 of the serial communication unit cannot
be used at the same time. Accordingly, have in mind that both the GOT and peripheral
equipment having the GPP function cannot be connected at the same time to one serial
communication unit and that two GOT units cannot be connected to one ser ial
communication unit at the same time.
CH connected to GOT
Contents of setting
CH1
CH2
Summary of Contents for A953GOT-LBD-M3-H
Page 4: ...A953 HANDY GOT ii ...
Page 6: ...A953 HANDY GOT iv ...
Page 14: ...A953 HANDY GOT xii MEMO ...
Page 28: ...A953 HANDY GOT Introduction 1 1 8 MEMO ...
Page 42: ...A953 HANDY GOT Installation Wiring 2 2 14 MEMO ...
Page 58: ...A953 HANDY GOT Wiring and Handling of Switches 3 3 16 MEMO ...
Page 72: ...A953 HANDY GOT Specifications 4 4 14 MEMO ...
Page 80: ...A953 HANDY GOT CPU Direct Connection 6 6 6 MEMO ...
Page 98: ...A953 HANDY GOT Connection to PLC by Omron 8 8 10 MEMO ...
Page 104: ...A953 HANDY GOT Connection to PLC by Yaskawa Electric 9 9 6 MEMO ...
Page 108: ...A953 HANDY GOT Connection to PLC by Allen Bradley 10 10 4 MEMO ...
Page 130: ...A953 HANDY GOT Connection to PLC by Siemens 13 13 4 MEMO ...
Page 134: ...A953 HANDY GOT Diagnostics 14 14 4 MEMO ...
Page 141: ......