A953 HANDY GOT
Diagnostics 14
14-2
14.2
When an operation switch or emergency stop switch does not operate
When an operation switch or emergency stop switch does not operate, check the following
points.
•
Check whether external cables are connected correctly to the Handy GOT. (Refer to 2.2.2.)
•
While pressing and holding an operation switch or emergency stop switch, check the
conductivity between wires (pins) of the external cables, relay cable shown in the table
below.
If the conductivity is not given, wire breakage or poor contact is present in the external cable
or relay cable, or the circuits inside the Handy GOT may be damaged.
If it is suspected that the circuits inside the Handy GOT are damaged, consult with a
Mitsubishi Electric distributor.
*1 Connect an external cable to the Handy GOT, press and hold each switch, then check
the conductivity between pins or wires.
F9GT-HCAB-
M
25-pin D-sub (male) connector
*2 Connect an external cable and relay cable to the Handy GOT, press and hold each
switch, then check the conductivity between each pair of wires of the relay cable.
Switch
name
Signals whose conductivity is checked
Signal name
External cable
*1
Relay cable
*2
F9GT-HCAB5-150
F9GT-HCAB-3M
F9GT-HCAB1-3M
SW1
SW-COM and SW1
14 and 15
Fresh green and sky blue
SW-COM and SW1
SW2
SW-COM and SW2
14 and 16
Fresh green and black/white
SW-COM and SW2
SW3
SW-COM and SW3
14 and 17
Fresh green and red/white
SW-COM and SW3
SW3
SW-COM and SW4
14 and 18
Fresh green and green/white
SW-COM and SW4
ES1
ES1 and ES1
21 and 22
Brown/white and yellow/white
ES1 and ES1
1
13
14
25
Summary of Contents for A953GOT-LBD-M3-H
Page 4: ...A953 HANDY GOT ii ...
Page 6: ...A953 HANDY GOT iv ...
Page 14: ...A953 HANDY GOT xii MEMO ...
Page 28: ...A953 HANDY GOT Introduction 1 1 8 MEMO ...
Page 42: ...A953 HANDY GOT Installation Wiring 2 2 14 MEMO ...
Page 58: ...A953 HANDY GOT Wiring and Handling of Switches 3 3 16 MEMO ...
Page 72: ...A953 HANDY GOT Specifications 4 4 14 MEMO ...
Page 80: ...A953 HANDY GOT CPU Direct Connection 6 6 6 MEMO ...
Page 98: ...A953 HANDY GOT Connection to PLC by Omron 8 8 10 MEMO ...
Page 104: ...A953 HANDY GOT Connection to PLC by Yaskawa Electric 9 9 6 MEMO ...
Page 108: ...A953 HANDY GOT Connection to PLC by Allen Bradley 10 10 4 MEMO ...
Page 130: ...A953 HANDY GOT Connection to PLC by Siemens 13 13 4 MEMO ...
Page 134: ...A953 HANDY GOT Diagnostics 14 14 4 MEMO ...
Page 141: ......