A953 HANDY GOT
Connection to PLC by Sharp 11
11-2
11.2
Initial setting
11.2.1
When GOT is directly connected to PLC CPU
When connecting the GOT directly to the PLC CPU, the communication setting is required at
first for the communication port. Using a peripheral tool, set as shown below to the system
memory in the PLC CPU.
For the details of the setting method, refer to the INSTRUCTION MANUAL of the PLC by
Sharp.
1) When the JW-22CU, the JW-70CUH or the JW-100CUH is used
Setting item
System memory
address
Contents of setting
Setting of
communication
port
#236
Set the transmission speed, the parity and the stop bit using
bits D0 to D5 as shown below.
#237
Set the station No. as shown below.
− −
1
1
0
0
0
1
D6 D5 D4 D3 D2 D1 D0
D7
#236
Transmission specifications
(9600 bps)
Parity (even)
Stop bit (2 bits)
1
#237
Station No. (1)
Summary of Contents for A953GOT-LBD-M3-H
Page 4: ...A953 HANDY GOT ii ...
Page 6: ...A953 HANDY GOT iv ...
Page 14: ...A953 HANDY GOT xii MEMO ...
Page 28: ...A953 HANDY GOT Introduction 1 1 8 MEMO ...
Page 42: ...A953 HANDY GOT Installation Wiring 2 2 14 MEMO ...
Page 58: ...A953 HANDY GOT Wiring and Handling of Switches 3 3 16 MEMO ...
Page 72: ...A953 HANDY GOT Specifications 4 4 14 MEMO ...
Page 80: ...A953 HANDY GOT CPU Direct Connection 6 6 6 MEMO ...
Page 98: ...A953 HANDY GOT Connection to PLC by Omron 8 8 10 MEMO ...
Page 104: ...A953 HANDY GOT Connection to PLC by Yaskawa Electric 9 9 6 MEMO ...
Page 108: ...A953 HANDY GOT Connection to PLC by Allen Bradley 10 10 4 MEMO ...
Page 130: ...A953 HANDY GOT Connection to PLC by Siemens 13 13 4 MEMO ...
Page 134: ...A953 HANDY GOT Diagnostics 14 14 4 MEMO ...
Page 141: ......